Selection & Sizing

How to size a gear coupling

Sizing is four independent checks, not one calculation: continuous torque, peak torque, bore capacity and speed. All four must pass, and the one that fails a selection most often is not torque — it is bore. This article works a 132 kW drive through all four with the arithmetic shown.

Author
Priyansh Thummar, Editor
Dates
Published · Last updated
Reading time
5 minutes

1. Four checks, not one calculation

Sizing a gear coupling is arithmetic, but it is four separate pieces of arithmetic, and a selection is only valid when all four pass:

  • Continuous torque — whether the teeth survive normal running.
  • Peak torque — whether they survive the start, the trip and the upset.
  • Bore capacity — whether the coupling physically fits the two shafts it has to join.
  • Speed — whether the selection needs balancing, and whether it can be run at that speed at all.

Engineers reliably do the first and reliably skip at least one of the other three. The order below is deliberate in one respect only: bore is worth checking early, because when it governs, it governs, and everything upstream has to be redone.

2. Nominal torque from power and speed

Power and speed give torque directly. For power in kilowatts and speed in revolutions per minute, the working form carries a constant of 9550 — which is simply 60 000 ÷ 2π, folded in so the units come out in newton metres.

Tnom [N·m] = 9550 × P [kW] ÷ n [rev/min]

Nominal torque at the coupling. For the worked example — 132 kW at 1480 rev/min — this gives 9550 × 132 ÷ 1480 = 852 N·m. Where the drive passes through a gearbox, the coupling on the slow-speed side sees the output speed and the output torque, which is a different and much larger number.

2.1 Rated power or absorbed power?

The correct input is the driver's rated power, not the power the driven machine absorbs in normal service. A motor will deliver its rated torque into a fault, and during a direct-on-line start it delivers a substantial multiple of it — entirely independently of what the pump was drawing the moment before.

Sizing on absorbed power produces a coupling that is adequate for the duty as described and inadequate for the event that actually breaks couplings. The exception that proves the rule: where the driver is deliberately oversized for future capacity, sizing on the full rating is still correct, because the day the capacity is used, nobody re-selects the coupling.

3. Applying the service factor

The service factor is routinely misread as a safety margin. It is not. It describes the character of the load rather than its magnitude. A centrifugal pump and a reciprocating compressor drawing identical average power impose entirely different peak loading on the tooth flanks, because one applies torque smoothly and the other applies it in pulses with a reversal component.

It is not there to cover uncertainty in the power figure. Inflating it because the load is poorly understood hides a question rather than answering it — and the honest response to an unknown duty is to characterise the duty, not to multiply by a larger number.

Tsel = Tnom × SF   →   852 × 1.5 = 1278 N·m

Selection torque is what gets compared against the coupling's published continuous rating — never against its peak rating. The service factor of 1.5 used here is for a centrifugal blower on a uniform electrical drive.

4. The peak check is separate

Gear couplings carry a peak or momentary rating distinct from the continuous one, and the events checked against it are transient: direct-on-line motor starting, a short circuit at the terminals, compressor surge, a two-phase reclosure, a driven machine seizing.

The magnitudes are large. Direct-on-line starting alone commonly produces two to two and a half times full-load torque at the shaft, and electrical transients can produce considerably more for a few cycles. The check therefore has to be made against the worst credible event for that train, not against a generic multiplier — a soft-started motor and a direct-on-line motor of identical rating impose entirely different peak duties on the same coupling.

Table 1 — The four checks, their input and what governs each
CheckCompared againstInput that governs itTypical failure if skipped
Continuous torquePublished continuous ratingDriver rated power, speed, service factorProgressive tooth flank wear
Peak torquePublished peak / momentary ratingStarting method, fault and surge casesTooth shear or hub burst on a transient
Bore capacityMaximum bore for the sizeLarger of the two shaft diameters, keyway depthSelection revised upward late, or a hub bored too thin
SpeedMaximum speed and balance thresholdRunning speed of the shaft the coupling sits onUnbalanced rotating load into the bearings
All four must pass independently. A selection is not conservative because one of them passes by a wide margin.

5. Bore — where selections actually fail

Every coupling size has a maximum bore, set by the material left between the bore surface and the root of the hub teeth. That limit does not scale with torque capacity in the same proportion, so on a great many drives the shaft diameter demands a larger coupling than the torque does.

A 132 kW four-pole motor in a standard frame carries an 80 mm shaft. The coupling has to accept that bore regardless of the fact that the torque calculation would have been satisfied by something smaller. When the two hubs sit on different shaft diameters — the normal case, not the exception — each is bored to its own shaft, and the size is governed by the larger of the two.

Keyway practice enters here too. The keyway removes material from the same wall the bore limit is protecting, so a shaft calling for a deeper-than-standard keyway can push a bore past the size's capability even when the nominal diameter is within it. The bore and keyway conventions themselves come from whichever standard governs the order — see AGMA 9002 for the inch-series practice and IS 3238 for the domestic metric convention.

6. Speed and the balance threshold

Every size carries a maximum speed, and beyond a threshold that varies by manufacturer and size, couplings require dynamic balancing. Running an unbalanced coupling above that threshold puts a rotating force into bearings that were never intended to carry it.

On a 1480 rev/min drive this check passes trivially. On a compressor train at ten thousand it governs the entire selection — and it is the reason high-speed service moves away from lubricated gear teeth altogether, toward the dry flexible elements covered in the gear versus disc comparison.

7. The example, end to end

A 132 kW, four-pole squirrel-cage motor at 1480 rev/min, started direct-on-line, driving a centrifugal blower. Motor shaft 80 mm, blower shaft 75 mm. Both machines on a common baseplate, ambient service, indoor.

Table 2 — 132 kW blower drive, worked through all four checks
StepWorkingResultGoverns?
Nominal torque9550 × 132 ÷ 1480852 N·m
Service factorCentrifugal blower, uniform electrical driver1.5
Selection torque852 × 1.51278 N·mNo
Peak caseDOL start ≈ 2.5 × full-load torque≈ 2130 N·m vs peak ratingNo, if peak rating ≥ 2 × continuous
Bore requiredmax(80 mm motor, 75 mm blower)80 mmYes — sets the size
Speed1480 rev/min vs size maximumWell insideNo
Bore governs this selection, not torque. The size that accepts an 80 mm bore has a continuous rating comfortably above 1278 N·m — which is the normal outcome on a general-industrial drive, and the reason the bore check belongs early rather than last.

The size call is then made by reading down a manufacturer's rating table for the first size that satisfies all of: continuous rating ≥ 1278 N·m, peak rating ≥ 2130 N·m, maximum bore ≥ 80 mm, maximum speed ≥ 1480 rev/min. If the first size satisfying the bore requirement also satisfies the torque requirements — as it does here — the selection is complete, and there is nothing to be gained by going larger.

Two things remain before the order is placed, and neither is a torque question. The misalignment capacity at the chosen size has to cover the angular, parallel and axial movement the installation will actually see, and the axial travel has to cover thermal growth of the train between cold and running conditions.

Working the same arithmetic against a specific range rather than in the abstract? Our publisher, Super Mech Industries, runs a gear coupling torque calculator against their own catalogue sizes. This article is the method; that is the tool.

Frequently asked

Do I size a gear coupling on motor rated power or on absorbed power?
On the driver's rated power, not the power the driven machine happens to absorb. The coupling has to survive whatever the driver can deliver into a fault, and a motor will deliver its full rated torque — and considerably more during a direct-on-line start — regardless of what the pump was drawing beforehand. Sizing on absorbed power leaves no margin for the condition that actually breaks couplings.
What does the service factor actually account for?
It accounts for the character of the load rather than its magnitude: torsional shock, reversals, cyclic variation and the duty cycle of the driven machine. A centrifugal pump and a reciprocating compressor drawing identical average power impose very different peak loading on the coupling teeth, and the service factor is what separates them. It is not a safety factor and it is not there to cover uncertainty in the power figure.
Why does a coupling that passes the torque check still not fit?
Because bore capacity and torque capacity scale differently. A coupling size has a maximum bore set by the wall thickness left between the bore and the root of the hub teeth, and on many drives the shaft diameter demands a larger size than the torque does. Checking bore before torque saves the rework of a selection that has to be revised upward anyway.
How much margin should a gear coupling selection carry?
Enough to pass all four checks with the service factor applied, and no more. Oversizing past that adds mass and inertia at the shaft end, increases the overhung moment on the bearings, and can move the train's torsional natural frequency somewhere less convenient. A coupling two sizes larger than the calculation requires is not two sizes more reliable.

References

  1. ANSI/AGMA 9000-D11, Flexible Couplings — Potential Unbalance Classification, for the balance thresholds referenced in §6.
  2. AGMA 9002-B04, Bores and Keyways for Flexible Couplings (Inch Series), for the bore and keyway practice in §5.
  3. IS 3238, Gear couplings (Bureau of Indian Standards), for the metric bore convention on domestic supply.
  4. Editorial note: the 132 kW example is constructed, not taken from a specific installation. The service factor of 1.5, the 2.5× direct-on-line starting multiplier and the 2× peak-to-continuous rating ratio are widely used order-of-magnitude values used here to make the method concrete — they are not ratings. Continuous and peak ratings, maximum bore and maximum speed are properties of a particular manufacturer's range and must be read from that range's tables. Per-size tables are to be inserted from catalogue data and confirmed at technical review.